Electrical safety at work in New Zealand: the law, testing and tagging, RCDs and power lines

Reviewed 20 November 2026 · Sources: New Zealand Legislation, WorkSafe New Zealand · 12 min read

Electrical safety at work in New Zealand is governed by two sets of law that work together: the Health and Safety at Work Act 2015 (HSWA), and the Electricity Act 1992 with the Electricity (Safety) Regulations 2010. The core rules are that electrical equipment must not be used if it is electrically unsafe, only authorised people may do prescribed electrical work, safe distances must be kept from electric lines, and an electric shock that exposes someone to serious risk must be notified to WorkSafe. Testing and tagging is a useful way to check equipment, but WorkSafe says it is not mandatory.

This guide sets out who regulates what, who can do electrical work, what testing and tagging does and does not achieve, RCDs and construction site supplies, working near power lines, and notification. It describes the law in force on 20 November 2026.

Key points

  • A person who owns or operates fittings or appliances must not use, or let anyone else use, them if they are electrically unsafe (Electricity (Safety) Regulations 2010, regulation 15).
  • Testing and tagging is not mandatory. WorkSafe says what the law requires is that equipment is electrically safe and maintained in a safe condition.
  • An appliance used by an employee or contractor is deemed electrically safe if it has a current tag issued in accordance with AS/NZS 3760 (regulation 26). That is one way to show safety, not the only way.
  • Only authorised people may do prescribed electrical work, such as installing, connecting or maintaining wiring and fittings or maintaining appliances, unless an exemption in sections 75 to 80 applies (Electricity Act 1992, section 74).
  • Anyone working on or near an electric line must keep the safe distances in NZECP 34 (regulation 17). For low voltage service lines, WorkSafe says isolation is the safest option.
  • An electric shock that exposes a person to a serious risk is a notifiable incident under HSWA section 24, and WorkSafe must be told as soon as possible.

Which laws cover electrical safety at work?

Electricity at work sits under two regimes. WorkSafe is the regulator for both: it receives notifications under HSWA and under section 16 of the Electricity Act, and electrical workers must tell WorkSafe about immediate dangers under regulation 19 of the Electricity (Safety) Regulations.

The law on electrical safety at work, as in force on 20 November 2026
InstrumentWhat it does
Health and Safety at Work Act 2015The general duties: manage risk so far as is reasonably practicable (section 30), provide safe plant, a safe work environment, safe systems of work and the training workers need (section 36), and notify notifiable events, including an electric shock that exposes someone to serious risk (sections 24 and 56).
Electricity Act 1992Restricts prescribed electrical work to authorised people (section 74), sets up the Electrical Workers Registration Board (section 148), and requires serious electrical accidents to be notified to WorkSafe (section 16).
Electricity (Safety) Regulations 2010Define when installations, fittings and appliances are electrically safe or unsafe, prohibit using unsafe equipment (regulation 15), require control of contact with live parts (regulation 16) and safe distances from electric lines (regulation 17), and set the deemed-safe rules for tags and RCDs (regulations 24 to 26).
Codes and standards cited in the RegulationsSchedule 2 of the Regulations cites, among others, NZECP 34:2001 (electrical safe distances) and AS/NZS 3760:2022 (in-service safety inspection and testing of electrical equipment and RCDs). Regulation 25 refers to AS/NZS 3012 for construction sites.

Under regulation 16, a person who has control of works, installations, fittings, appliances or associated equipment must minimise, so far as is reasonably practicable, the risk of injury from direct or indirect contact between live exposed conductive parts and any person. Under regulation 15(1A), a person must not hire out or lease fittings or appliances that are electrically unsafe at the start of the hire.

Who can do electrical work in NZ?

Section 74 of the Electricity Act 1992 says a person must not do, or assist in doing, prescribed electrical work unless authorised. Authorised people are those registered and holding a current practising licence, or working under a provisional licence or an employer licence, within any limits set by regulations. There are limited exemptions in sections 75 to 80, for example for some work done under supervision and some domestic electrical wiring work, each with its own conditions.

Schedule 1 of the Electricity (Safety) Regulations defines prescribed electrical work. It includes installing, connecting or maintaining conductors and fittings in installations, connecting or disconnecting fittings to a power supply other than by plug and socket, maintaining appliances, and the testing, certification, inspection and supervision of that work. Schedule 1 also lists work that is not prescribed electrical work, for example operating or switching equipment, including replacing fuse links, and some work on extra-low voltage equipment.

The Electrical Workers Registration Board designates the classes of registration and what each class may do (section 149). Before engaging someone to do electrical work, check they hold the right registration and a current practising licence for that work. WorkSafe’s construction guidance gives practical examples: only a licensed electrical worker can install, connect, modify or move a builder’s temporary supply, and a licensed electrician or electrical inspector must install a switchboard RCD.

Is testing and tagging a legal requirement?

No. WorkSafe says testing and tagging electrical appliances is one useful way to check equipment is safe, but it is not mandatory. What is legally required is that equipment is electrically safe and maintained in a safe condition. Testing gives a snapshot of how safe an appliance is at the time it is tested; it does not guarantee future safety.

The link to the law is regulation 26 of the Electricity (Safety) Regulations. A fitting or appliance in use, or available for use, by an employee or contractor of its owner is deemed to be electrically safe if it has a current tag issued in accordance with AS/NZS 3760. For hired or leased equipment, it is also deemed safe if, when first made available, it is supplied through a portable RCD or a circuit protected by an electrically safe RCD that provides protection from electric shock. A current tag is therefore a recognised way to show equipment is safe, not a duty in itself.

Testing and tagging: what WorkSafe says
QuestionWorkSafe’s answer
Who decides whether to test and tag?The PCBU. It can buy test equipment and train a worker, or engage a third party.
Does the tester need to be an electrician?No. The person must have the knowledge and skills to do it correctly and understand the standards involved, but need not be a registered electrical worker. Only a registered electrical worker can fix problems the testing reveals.
How often?It depends on the equipment and the workplace. Equipment used outside and in damp conditions on a construction site needs more frequent testing than a computer in an office.
Is a tag enough on its own?No. Look at cords, plugs and tools regularly for damage, and remember equipment still needs RCD protection in some circumstances, such as outside in the damp.

A sensible approach for most workplaces: keep an equipment list, decide test intervals based on the conditions of use, train workers to check leads and tools before each use, give them a simple way to report and tag out damaged gear, and keep the test records. Hire companies must not hire out unsafe equipment, and WorkSafe says they are responsible for testing and tagging hire equipment before you hire it.

RCDs, PSOAs and construction site supplies

A residual current device (RCD) cuts the supply when it detects current flowing to earth above a set level. WorkSafe explains that an RCD gives a high level of personal protection and can disconnect the supply in many situations where someone would otherwise receive a fatal shock, but that it minimises the risk rather than eliminating it. Regulation 24 sets trip-time and other limits for RCDs that protect against electric shock; an RCD that does not meet them is deemed electrically unsafe.

Construction sites carry extra rules. Under regulation 25, installations, fittings and appliances on construction sites are deemed electrically safe if they comply with AS/NZS 3012 and are used in accordance with it. WorkSafe’s guide for small construction sites says:

  • all hand-held appliances, light sources and other electrical equipment on a construction site must have protection against electric shock, and all electrical equipment should be RCD-protected
  • before a builder’s temporary supply is used, an electrician must provide a Certificate of Compliance, a Record of Inspection and an Electrical Safety Certificate; it then needs a periodic assessment at least every six months
  • a portable socket-outlet assembly (PSOA) must be marked as compliant with AS/NZS 3012, fed by a heavy-duty sheathed flexible cord no longer than 2 metres, have its RCD tested with the test button every day before use, and be tested by an electrician at least every three months
  • domestic multi-boards should never be used on a construction site
  • contractors sharing a site supply must make sure their equipment is safe for others too, and businesses with overlapping duties must consult, cooperate and coordinate on electrical risks.

See overlapping duties for how to share these responsibilities with other businesses on site.

Working near overhead power lines and buried cables

Regulation 17 of the Electricity (Safety) Regulations says a person carrying out construction, building, excavation or other work on or near an electric line must maintain safe distances in accordance with NZECP 34, the New Zealand Electrical Code of Practice for Electrical Safe Distances. It is an offence for the person doing the work, the person controlling it, and the owner or controller of the line, equipment or machinery involved if the safe distances are not kept.

WorkSafe’s guide to working near low voltage overhead electric lines (the service line crossing into a property) says:

  • the safest option is to have the supply to the property isolated before work starts; electricity retailers have contractors who can do this on request
  • if isolation is not possible, workers must keep a minimum approach distance (MAD) of at least 4 metres from the line, or at least 0.5 metres with written consent from the property owner
  • for any work that could bring a worker, tools or equipment closer than 0.5 metres, the supply must be isolated
  • there are separate MADs for temporary structures such as scaffolding and for mobile plant such as cranes and elevating work platforms
  • never use a conductive object, such as a metal tape measure, to measure a MAD, and check for generators or solar systems that could back-feed an isolated property.

For high voltage lines or any overhead lines owned by an electricity distributor, WorkSafe says to seek permission from the distributor before working nearby. WorkSafe’s construction guidance also says hidden electricity cables and other utilities, such as gas pipes, should be located, shown on plans and marked. Plan scaffolding, ladders and mobile plant around lines as part of your working at height controls.

Managing electrical risk day to day

Electrical risk follows the same HSWA approach as any other: eliminate it if you can, otherwise minimise it so far as is reasonably practicable, and involve workers. Practical controls include:

  • Isolation before work. De-energise, lock out and test before anyone works on or near electrical equipment. Live work should be the rare exception, planned and done only by authorised people.
  • RCD protection for portable equipment, especially outdoors, in wet or damp areas and on construction sites. Test RCDs regularly.
  • Right equipment for the conditions. Use equipment rated for the environment, battery tools where they remove trailing leads, and industrial-grade leads and outlets where conditions are harsh.
  • Pre-use checks. Train workers to look for damaged cords, plugs and casings, scorch marks and exposed conductors, and to tag out anything faulty.
  • Lead management. Keep leads off the ground and away from water, sharp edges and vehicle routes.
  • Competent people. Use authorised electrical workers for prescribed electrical work and keep certificates of compliance for installation work.
  • Emergency readiness. Make sure people know how to isolate the supply before touching someone who has had a shock, and that first aiders are trained in CPR. See first aid requirements.

Notifying electric shocks and electrical accidents

Section 24 of HSWA says a notifiable incident includes an unplanned or uncontrolled incident that exposes a worker or any other person to a serious risk to their health or safety arising from an immediate or imminent exposure to an electric shock. Nobody needs to be hurt. WorkSafe’s construction guidance puts it plainly: you must notify WorkSafe if an electric shock exposes a person to a serious risk to their health and safety, or if someone is seriously injured, as soon as possible, even if emergency services attend. An injury from electricity that needs hospital admission, or a death, is notifiable in its own right.

Section 16 of the Electricity Act separately requires an accident caused wholly or partly by electricity that results in serious harm to a person, or damage that makes a place unusable for its purpose, to be notified to WorkSafe. Section 16(6) says notifying under section 56 of HSWA counts as compliance. Preserve the site and keep a record. See notifiable events.

Frequently asked questions

Is test and tag a legal requirement in New Zealand?

No. WorkSafe says testing and tagging is not mandatory; the legal requirement is that electrical equipment is electrically safe and maintained in a safe condition. A current tag issued under AS/NZS 3760 is one way the Regulations deem equipment used by employees or contractors to be safe.

Does an electrician have to do testing and tagging?

No. WorkSafe says the tester must have the knowledge and skills to do it correctly and understand the standards, but need not be a registered electrical worker. Only a registered electrical worker can fix the faults testing finds.

How often should electrical equipment be tested?

There is no single legal interval. WorkSafe says it depends on the equipment and the workplace: harsh, damp or outdoor conditions need more frequent testing than an office.

Can a worker change a plug or repair a lead?

Maintaining appliances is prescribed electrical work, which only authorised people may do. Schedule 1 of the Regulations has narrow exceptions, so the safe rule at work is to tag out damaged leads and tools and have them repaired by an authorised person or replaced.

How close can I work to an overhead power line?

You must keep the safe distances in NZECP 34. For a low voltage service line on a property, WorkSafe says isolate the supply if you can; otherwise keep at least 4 metres away, or 0.5 metres with the property owner’s written consent. Closer than 0.5 metres needs isolation.

Do I have to notify WorkSafe if someone gets an electric shock?

Yes, if the shock exposed them to a serious risk to their health or safety, even if they were not hurt. It is a notifiable incident under HSWA section 24. Notify as soon as possible and preserve the site.

Do we need RCDs on all equipment?

On construction sites, WorkSafe says all hand-held equipment must have protection against electric shock and all electrical equipment should be RCD-protected. Elsewhere, RCD protection is needed in some circumstances, such as outdoors in the damp, and is a sensible control for portable equipment.

Who regulates electrical safety in New Zealand?

WorkSafe New Zealand, under both HSWA and the Electricity Act 1992 and its regulations. The Electrical Workers Registration Board, set up under the Electricity Act, designates the classes of registration for electrical workers.

Sources

This guide is general information about New Zealand health and safety law and WorkSafe guidance, written for businesses. It is not legal advice, and it is not published or endorsed by WorkSafe New Zealand. Check the current legislation at legislation.govt.nz and take advice on your own situation.